Specifications SiBE31-801_C25 Specifications1-2 ELECTRICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVEPowerSupply Name VEPhase 1Frequency Hz 50Voltage V 220-240Current Minimum circuit amps(MCA) A 0.30 0.30 0.30 0.50Maximum fuse amps(MFA) A 15.00Full load amps (FLA) A 0.20 0.20 0.20 0.40Voltagerange Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below orabove listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 × FLAMFA<= 4 × FLAnext lower standard fuse rating minimum 15Aselect wire size based on the MCAinstead of a fuse, use a circuit breakerFor more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".Finally, click on the document title of your choice.