SiBE31-801_C Troubleshooting by Indication on the Remote ControllerTroubleshooting 2784.37 “L5” Outdoor Unit: Momentary Overcurrent of InverterCompressorRemoteControllerDisplayL5ApplicableModelsRTSQ8P~16P (Outdoor Unit)Method ofMalfunctionDetectionMalfunction is detected from current flowing in the power transistor. (32.3 A)MalfunctionDecisionConditionsWhen an excessive current flows in the power transistor.(Instantaneous overcurrent also causes activation.)SupposedCauses Defect of compressor coil (disconnected, defective insulation) Compressor start-up malfunction (mechanical lock) Defect of inverter PCB