ESIE05-03 General FunctionalityPart 2 – Functional Description 2–23324511.16 PMV ControlOutline When the automatic mode is selected on the remote-controller, the unit will automatically activate thePMV control.The PMV index is a calculated average comfort level.Refer to ISO 7730 for details.Function An optimized indoor temperature will be calculated using the following inputs:P Outdoor air temperatureP Indoor air temperatureP Remote controller set temperatureIn practice, the set point will be moved with 1 or 2 degrees whenever the conditions change. This willresult in a combination of power saving and increased comfort level.PMV control can be disabled by changing the field settings:From: 11(21)-4-01 to: 11(21)-4-02