Test Run and Operation Data ESIE05-034–36 Part 4 – Commissioning and Test Run31453.1 General Operation DataGuide Lines forOptimal OperationConditionThe operation value guide lines when operating under standard conditions (at Rated frequency) bypushing the test run button on the remote controller are as given in the table below.Indoor Unit Fan: “H” Operation Compressor: Rated FrequencyHighPressure(Mpa)LowPressure(Mpa)DischargePipeTemperature(°C)SuctionTemperature(°C)Indoor UnitSide:DifferentialBetweenSuction Tem-perature andDischargeTemperature(°C)Outdoor UnitSide:DifferentialBetweenSuction Tem-perature andDischargeTemperature(°C)Cooling 26 bar ~34 bar6 bar ~10 bar60~100 –2~10 8~18 7~12Heating 25 bar ~32.6 bar5.3 bar ~7.5 bar60~100 –6~2 14~30 2~6