ESIE05-03 Field settingsPart 4 – Commissioning and Test Run 4–1334512.4 Overview of the Field Settings on the Indoor UnitsField settings The table below contains the possible field settings of all indoor units.ModeNo.Firstcode No. Description of the settingSecond code No.01 02 03 0410 or 20 0 Filter counter Lightcontaminationheavycontamination— —1 Filter type Long Super long External Oil mist2 Remote thermistor of theremote controllerTH1 = rem.controllerTH1 = airreturn— —3 Filter display Filter indic. No filter indic. — —11 or 21 0 Number indoor to 1 outdoor Pair Twin Triple Double twin1 Unified or indiv. set twin Group setting Indiv. setting — —2 Fan OFF at thermostat OFF LL-speed OFF — —12 or 22 0 KRP1B51/52/53 X1/X2 output ThermostatONOption Operation Malfunction1 EKRORO Forced OFF ON/OFF oper-ation— —3 Fan speed heating thermostatOFFLL-speed Set speed — —5 Automatic restart Disabled Enabled — —13 or 23 0 Ceiling height setting Normal High Extra high —≤ 2.7 m >2.7≤3.0 m >3.0≤3.5 m —1 Selection of air flow direction(setting for when a blockingpad kit has been inst alled).4-way flow 3-way flow 2-way flow—3 Horizontal discharge grill Enabled Disabled — —4 Air flow direction adjust rangesettingDraft preven-tionStandard Ceil soil pre-vention—5 Field fan speed changeover airoutlet (domestic only)Standard Option 1 Option 2 —6 External static pressure Normal High Low —14 or 24 0 Additional timer to guard timer 0 s 5 s 10 s 15 s1b(Only incase ofBRC1D52)0 Permission level setting Level 2 Level 3 — —1 Leave home function NotpermittedPermitted — —2 Thermostat sensor in remotecontroller (for limit operationand leave home function only)Use Not use — —