ESIE05-03 Indoor Unit Functional ConceptPart 2 – Functional Description 2–33324512.6 Draft Avoidance Control 2Purpose The purpose of the draft avoidance control 2 is to avoid draft when the flap is moving.Starting conditions The draft avoidance control 2 is activated when:P Hot start is finished, orP Cold air prevention control is finished.Time chart If the fan speed is set to "H", the fan turns at low speed for a certain amount of time.Used input Draft avoidance control 2 uses the following inputs:FanFlapHot start finishedSettingOFF/LLLHPo0TT = 24 sFCQ: T = 5sInput Connection onindoor PCBConnection onoutdoor PCBLimit switch for flap 33S —No. of fan turns X26A —