Field settings ESIE05-034–26 Part 4 – Commissioning and Test Run31452.12 I-Demand FunctionPurpose Set a limitation towards the power consumption from the system.(e.g. budget control, limit powerconsumption during peak moments,..)Setting 3 different demand setting can be selected by using terminal X801M:P Demand 1 → Close contact between COM and contact 1P Demand 2 → Close contact between COM and contact 2P Demand 3 → Close contact between COM and contact 3Power supply connector(on outdoor PCB X77A)Output on X801M =12VDC, 12mAMaximum wire length =100 meterTransmission connector(on outdoor PCB X6A)