Field settings ESIE05-034–28 Part 4 – Commissioning and Test Run31452.13 Setting for Low Humidity ApplicationPurpose Can be set when using the RZQ units for year round cooling in low humidity applications such ascomputerrooms (EDP rooms), technical rooms, etc...to increase the capacity of the unit.Definition of LowHumidity AreaCaution When using the "LH settings" outside the "Low Humidity Area" there is an increased risk of iceaccumulation on the indoor coil or water blowing out from the indoor unit.RelativeHumidity(%)Setting is only allowed in this areaIndoor side temperature DB (°C)