Additional Checks for Troubleshooting ESIE05-033–108 Part 3 – Troubleshooting313455.6 R3T: Resistance Conversion Table (Discharge Pipe Sensor)Temperature –resistanceThe table below is the thermistor (R3T) temperature – resistance conversion table.Temp.(°C)Resist.(kΩ)Temp.(°C)Resist.(kΩ)Temp.(°C)Resist.(kΩ)— — 60.0 52.8 130.0 5.4—-6.0-4.0-2.0—1120.01002.5898.662.064.066.068.048.945.342.039.0132.0134.0136.0138.05.44.84.64.30.0 806.5 70.0 36.3 140.0 4.12.04.06.08.0724.8652.2587.6530.172.074.076.078.033.731.429.227.2142.0144.0146.0148.03.93.73.53.310.0 478.8 80.0 25.4 150.0 3.212.014.016.018.0432.9392.0355.3322.482.0———23.7———152.0154.0156.0158.03.02.92.72.620.0 292.9 — — 160.0 2.522.024.026.028.0266.3242.5221.0201.692.094.096.098.016.915.814.813.9162.0164.0166.0168.02.32.52.12.030.0 184.1 100.0 13.1 170.0 1.932.034.036.038.0168.3154.0141.0129.3102.0104.0106.0108.012.311.510.810.2172.0174.0176.0178.01.91.81.71.640.0 118.7 110.0 9.6 180.0 1.542.044.046.048.0109.0100.292.284.9112.0114.0116.0118.09.08.58.07.6—50.0 78.3 120.0 7.152.054.056.048.072.266.761.657.0122.0124.0126.0128.06.76.46.05.7