Field settings ESIE05-034–10 Part 4 – Commissioning and Test Run31452.2 How to Change the Field Settings with the Wired Remote ControllerInstallationconditionsThe field settings have to be changed with the remote controller according to the installationconditions.Wired remotecontroller(BRC1D527)The illustration below shows the wired remote controller.Components The table below contains the components of the wired remote controller.129325221110373527261214173424520 211816 13 15 19323130292843633823 76No. Component No. Component1 ON/OFF button 20 Air flow direction icon2 Operation lamp 21 Not available3 Operation mode icon 22 Fan speed icon4 Ventilation mode icon 23 Defrost/hotstart mode icon5 Ventilation icon 24 Air filter cleaning time icon6 Air cleaning icon 25 Element cleaning time icon7 Leave home icon 26 Ventilation mode button8 External control icon 27 Ventilation amount button9 Change-over under centralised control icon 28 Inspection/test operation button10 Day of the week indicator 29 Programming button11 Clock display 30 Schedule timer button12 Maximum set temperature 31 Time adjust button13 Minimum set temperature 32 Temperature adjust buttons14 Schedule timer icon 33 Operation change/ button15 Action icons 34 Setpoint/limit button16 Off icon 35 Fan speed button17 Inspection required 36 Air flow direction adjust button18 Set temperature display 37 Air filter cleaning time icon reset19 Setting