P500 P560 P630 P710 P800 P1M0High/normal load* HO NO HO NO HO NO HO NO HO NO HO NOTypical shaft output at 400 V [kW] 450 500 500 560 560 630 630 710 710 800 800 1000Typical shaft output at 460 V [hp] 600 650 650 750 750 900 900 1000 1000 1200 1200 1350Enclosure IP21/IP54 with or withoutoptions cabinet F1/F3 F2/F4Output currentContinuous (at 3x380-440 V) [A] 800 880 880 990 990 1120 1120 1260 1260 1460 1460 1720Intermittent (at 3x380-440 V) [A] 1200 968 1320 1089 1485 1232 1680 1386 1890 1606 2190 1892Continuous (at 3x441-480 V) [A] 730 780 780 890 890 1050 1050 1160 1160 1380 1380 1530Intermittent (at 3x441-480 V) [A] 1095 858 1170 979 1335 1155 1575 1276 1740 1518 2070 1683Continuous kVA (at 400 V AC) [kVA] 554 610 610 686 686 776 776 873 873 1012 1012 1192Continuous kVA (at 460 V AC) [kVA] 582 621 621 709 709 837 837 924 924 1100 1100 1219Max. input currentContinuous (3x380-440 V) [A] 779 857 857 964 964 1090 1090 1227 1227 1422 1422 1675Continuous (3x441-480 V) [A] 711 759 759 867 867 1022 1022 1129 1129 1344 1344 1490Max. pre-fuses1) [A] 1600 2000 2500Max. cable sizeMotor (mm2/AWG2) 5)) 8x150 (8x300 mcm) 12x150 (12x300 mcm)Mains, F1/F2 (mm2/AWG2) 5)) 8x240 (8x500 mcm)Mains, F3/F4 (mm2/AWG2) 5)) 8x456 (8x900 mcm)Loadshare (mm2/AWG2) 5)) 4x120 (4x250 mcm)Brake (mm2/AWG2) 5)) 4x185 (4x350 mcm) 6x185 (6x350 mcm)Estimated power loss at 400 V AC atrated max load [W] 3) 9031 10162 10146 11822 10649 12512 12490 14674 14244 17293 15466 19278Estimated power loss at 460 V AC atrated max load [W] 3) 8212 8876 8860 10424 9414 11595 11581 13213 13005 16229 14556 16624Max. added losses A1 RFI, CB ordisconnect, and contactor, F3/F4 893 963 951 1054 978 1093 1092 1230 2067 2280 2236 2541Max. panel options losses 400Weight, enclosure IP2, kg [lbs.] 1017/1318 [2242/2905] 1260/1561 [2778/3441]Weight, enclosure IP54, kg [lbs.]Weight, rectifier module, kg [lbs.] 102 [224] 102 [224] 102 [224] 102 [224] 136 [299] 136 [299]Weight, inverter module, kg [lbs.] 102 [224] 102 [224] 102 [224] 136 [299] 102 [224] 102 [224]Efficiency4) 0.98Output frequency [Hz] 0-590Heatsink overtemp. trip [°C] 95Power card ambient trip [°C] 75*High overload=150% current for 60 s, Normal overload=110% current for 60 sTable 8.3 Technical Specifications, F1-F4, Mains Supply 3x380-480 V AC1) For type of fuse, consult the Operating Instructions.2) American Wire Gauge.3) The typical power loss is at normal conditions and expected to be within± 15% (tolerance relates to variety in voltage and cable conditions.)These values are based on a typical motor efficiency (IE2/IE3 border line). Lower efficiency motors add to the power loss in the frequencyconverter and the opposite is also true. If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typicalcontrol card power consumptions are included. Further options and customer load can add up to 30 W to the losses (though typically only 4 Wextra for a fully loaded control card or options for slot A or slot B, each).4) Measured using 5 m screened motor cables at rated load and rated frequency.5) Wiring terminals on N132, N160, and N315 frequency converters cannot receive cables one size larger.General Specifications and ... Design Guide168 Danfoss A/S © Rev. 06/2014 All rights reserved. MG20Z20288