8.1.2 Mains Supply 3x525-690 V ACN75K N90K N110K N132 N160High/normal load* HO NO HO NO HO NO HO NO HO NOTypical shaft output at 550 V [kW] 45 55 55 75 75 90 90 110 110 132Typical shaft output at 575 V [hp] 60 75 75 100 100 125 125 150 150 200Typical shaft ouptut at 690 V [kW] 55 75 75 90 90 110 110 132 132 160Enclosure IP20 D3hEnclosure IP21/IP54 D1hOutput currentContinuous (at 550 V) [A] 76 90 90 113 113 137 137 162 162 201Intermittent (60 s overload) (at 550 V)[A] 122 99 135 124 170 151 206 178 243 221Continuous (at 575/690 V) [A] 73 86 86 108 108 131 131 155 155 192Intermittent (60 s overload) (at 575/690V) [kVA] 117 95 129 119 162 144 197 171 233 211Continuous kVA (at 550 V) [kVA] 72 86 86 108 108 131 131 154 154 191Continuous kVA (at 575 V) [kVA] 73 86 86 108 108 130 130 154 154 191Continuous kVA (at 690 V) [kVA] 87 103 103 129 129 157 157 185 185 229Max. input currentContinuous (at 550 V) [A] 77 89 89 110 110 130 130 158 158 198Continuous (at 575 V) [A] 74 85 85 106 106 124 124 151 151 189Continuous (at 690 V) [A] 77 87 87 109 109 128 128 155 155 197Max. cable sizeMains, motor, brake, and load share(mm2/AWG2)) 2x95 (2x3/0)Max. external mains fuses [A] 160 315Estimated power loss at 575 V [W]3) 1098 1162 1162 1428 1430 1740 1742 2101 2080 2649Estimated power loss at 690 V [W]3) 1057 1204 1205 1477 1480 1798 1800 2167 2159 2740Weight, enclosure IP20, kg [lbs.] 125 [275]Weight, enclosures IP21/ IP54, kg [lbs.] 62 [135]Efficiency4) 0.98Output frequency [Hz] 0-590Heatsink overtemp. trip [°C] 110Power card ambient trip [°C] 75*High overload=150% current for 60 s, Normal overload=110% current for 60 s.Table 8.4 Technical Specifications, D1h/D3h, Mains Supply 3x525-690 V ACGeneral Specifications and ... Design GuideMG20Z202 Danfoss A/S © Rev. 06/2014 All rights reserved. 1698 8