Type Description Ordering no.External OptionsEthernet IP Ethernet 130B1119 130B1219Spare PartsControl board VLT® AQUADrive FC 202With Safe Stop Function 130B1167Control board VLT® AQUADriveFC 202Without Safe Stop Function 130B1168Accessory bag ControlTerminals130B02951) Only IP21/> 11 kWTable 4.5 Ordering Numbers: Options and AccessoriesOptions can be ordered as factory built-in options, see ordering information.For information on fieldbus and application option compatibility with older software versions, contact your Danfoss supplier.4.2.2 Advanced Harmonic FiltersHarmonic filters are used to reduce mains harmonics:• AHF 010: 10% current distortion• AHF 005: 5% current distortionFor detailed information on advanced harmonic filters, see the Advanced Harmonic Filters Design Guide.CodenumberAHF005IP00IP20CodenumberAHF010IP00IP20FiltercurrentratingTypicalmotorVLT model andcurrent ratingsLosses Acousticnoise Frame sizeAHF005 AHF010[A] [kW] [kW] [A] [W] [W] [dBA] AHF005 AHF010130B1446130B1251130B1295130B1214204 110 N110 204 1080 742 <75 X6 X6130B1447130B1258130B1369130B1215251 132 N132 251 1195 864 <75 X7 X7130B1448130B1259130B1370130B1216304 160 N160 304 1288 905 <75 X7 X7130B3153130B3152130B3151130B3136325 Paralleling for 355 kW 1406 952 <75 X8 X7130B1449130B1260130B1389130B1217381 200 N200 381 1510 1175 <77 X8 X7130B1469130B1261130B1391130B1228480 250 N250 472 1852 1542 <77 X8 X82x130B14482x130B12592x130B13702x130B1216608 315 N315 590 2576 1810 <80Table 4.6 Advanced Harmonic Filters 380-415 V, 50 Hz, D-frameHow to Order Design GuideMG20Z202 Danfoss A/S © Rev. 06/2014 All rights reserved. 634 4