if any one feedback is below the setpoint and decrease thespeed of the fan if all feedbacks are above the setpoint.Example 2 – Multi zone, multi setpointThe previous example can be used to illustrate the use of multizone, multi setpoint control. If the zones require different pres-sures for each VAV box, each setpoint may be specified in par.20-21, 20-22 and 20-23. By selectingMulti setpoint minimum,[5], in par. 20-20, Feedback Function, the PID Controller willincrease the speed of the fan if any one of the feedbacks is be-low its setpoint and decrease the speed of the fan if all feed-backs are above their individual setpoints.Sum [0] sets up the PID Controller to use the sum of Feedback1, Feedback 2 and Feedback 3 as the feedback.NB!Any unused feedbacks must be set toNo Func-tion in par. 20-00, 20-03, or 20-06.The sum of Setpoint 1 and any other references that are enabled(see par. group 3-1*) will be used as the PID Controller’s set-point reference.Difference [1] sets up the PID Controller to use the differencebetween Feedback 1 and Feedback 2 as the feedback. Feedback3 will not be used with this selection. Only setpoint 1 will beused. The sum of Setpoint 1 and any other references that areenabled (see par. group 3-1*) will be used as the PIDController’s setpoint reference.Average [2] sets up the PID Controller to use the average ofFeedback 1, Feedback 2 and Feedback 3 as the feedback.NB!Any unused feedbacks must be set toNo Func-tion in par. 20-00, 20-03, or 20-06. The sum ofSetpoint 1 and any other references that are en-abled (see par. group 3-1*) will be used as the PIDController’s setpoint reference.Minimum [3] sets up the PID Controller to compare Feedback1, Feedback 2 and Feedback 3 and use the lowest value as thefeedback.2. Parameter Description VLT ® AQUA Drive Programming Guide178 MG.20.O2.02 - VLT ® is a registered Danfoss trademark2