Grounding the J-SRX210 Services GatewayTo meet safety and electromagnetic interference (EMI) requirements and to ensureproper operation, you must adequately ground the J-SRX210 Services Gateway beforeconnecting power.Figure 23 on page 77 illustrates connecting a grounding cable to the services gateway.Figure 23: Grounding the J-SRX210 Services GatewayYou ground the device by connecting a grounding cable to earth ground and then attachingit to the chassis grounding points using one 6–32 UNC screw.Table 32 on page 77 lists the specifications of the grounding cable used with the device.Table 32: Grounding Cable Specifications for the Services GatewaySpecificationGrounding Requirement14 AWG single-strand wire cableGrounding cableUp to 4 AAmperage of grounding cableRing-type, vinyl-insulated TV14-6R lug orequivalentGrounding lugCAUTION: Before device installation begins, a licensed electrician must attach a cablelug to the grounding and power cables that you supply. A cable with an incorrectlyattached lug can damage the device (for example, by causing a short circuit).77Chapter 13: Connecting, Grounding, and Powering On the J-SRX210 Services Gateway