UPS Installation Plan and Unpacking3-20 Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerqualityConduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 3-7 or Table 3-8 forconduit recommendations.Per NEC article 300, 3(B), all three-phase conductors must be run in the same conduit. A ground wire must berun in the same conduit as the phase conductors.When running parallel wires in multiple conduits a ground wire must be run in each conduit in accordance withNEC Table 250.122.Conduit is sized to accommodate one ground conductor per conduit, sized in accordance withNEC Table 250.122.Conduit sizes listed are for copper wiring only.Table 3-7. Power Cable Conduit Recommendations for the Eaton 93PM-100-1 and Eaton 93PM-100-2 (N+1)UPS Model UPS Rating Voltage TerminalNumber of Wiresin ConduitMinimum ConduitTrade SizeNumber ofConduitsEaton 93PM-100-1Eaton 93PM-100-2 (N+1) 20 kW480 VacAC Input to UPS Rectifier and Bypass(A, B, C, Ground)4 3/4 1AC Output (Three Wire)(A, B, C, Ground)4 3/4 1DC Battery(Positive, Negative, Ground)5 2-1/2 1Eaton 93PM-100-1Eaton 93PM-100-2 (N+1)) 30 kW480 VacAC Input to UPS Rectifier and Bypass(A, B, C, Ground)4 1-1/4 1AC Output (Three Wire)(A, B, C, Ground)4 1 1DC Battery(Positive, Negative, Ground)5 2-1/2 1Eaton 93PM-100-1Eaton 93PM-100-2 (N+1) 40 kW480 VacAC Input to UPS Rectifier and Bypass(A, B, C, Ground)4 1-1/4 1AC Output (Three Wire)(A, B, C, Ground)4 1-1/4 1DC Battery(Positive, Negative, Ground)5 2-1/2 1Eaton 93PM-100-1Eaton 93PM-100-2 (N+1) 50 kW480 VacAC Input to UPS Rectifier and Bypass(A, B, C, Ground)4 1-1/4 1AC Output (Three Wire)(A, B, C, Ground)4 1-1/4 1DC Battery(Positive, Negative, Ground)5 2-1/2 1NOTE Wires per conduit include ground wire.