104 Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de43 DualGuard-S 20C643 DualGuard-S 20C6The DualGuard-S 20C6 in IP21 (IP31 optional) version withindividual cable entry in accordance with EN 50171 is sui-table for supplying up to 48 circuits for safety and escapesign luminaires 230V / 216V AC/DC in the power range upto 13.6KW. Two distribution outputs for mains and batteryenable the connection of a sub-stations of type DualGuardUS, DualGuard-S ESF30 and DualGuard-S SOU. The wiringsystem with rounded mounting fields does without classiccable ducts and, in combination with the natural ventilationand the large ventilation slots of the mounted modules,ensures a homogeneous control cabinet climate which hasbeen proven by heating tests in accordance with EN 61439-1 under nominal load conditions. The clear, self-explanatoryinternal modular field structure, taking contact protectioninto account, rounds off the appearance.The extensive catalogue of cabinet accessories such asspecial locks, door hinges right/left, cable glands, bases invarious heights, IP31 retrofit kits and IP54 on request offersthe right solution for most customer-specific requirementswithout long delivery times.The colour touch display with automatic test device andindividual luminaire monitoring with individual status andname indication per luminaire in connection with system-bound ECG / LED supply module including monitoringmodule without additional data line reports and recordsadditionally the operating status of the external phasemonitor modules, the insulation monitoring device as wellas the battery strings and when using the battery blockmonitoring technology of each individual battery block.1 2 3 4ABCD