13Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de6 Assembly and installation of the DualGuard-SCAUTION!!Always dispose of packaging materials in an environmentallyfriendly manner and in accordance with the applicable localdisposal regulations. If necessary, commission a recyclingcompany.Observe the handling instructions on the packaging!5.3 StoragePackages must be closed until assembly and stored inaccordance with the installation and storage markings onthe outside.Packages should only be stored ander the following condi-tions:• Do not store outdoors• Dry and dust-free storage• The storage location should be clean and tidy.• The storage time should be as short as possible in theinterest of the user (FIFO method).• The stacking of pallets or equipment is not permitted.6 Assembly and installation of the DualGu-ard-SWARNING! DANGER OF INJURY!Improper installation and installation can lead to serious per-sonal injury and/or damage to property. This work may there-fore only be carried out by authorised, instructed personnelfamiliar with the operation of the device and in compliancewith all safety regulations.• Ensure sufficient freedom of movement.• Pay attention to cleanliness and order at the workplace. Loo-se or loose components and tools are sources of accidents!• Ensure sufficient cooling of the system• Observe ambient conditions in accordance with protec-tion Typee and class (with regard to protection againstcontact with live parts and ingress of dust, foreign bodiesor moisture).• The cable length in a lighting circuit up to the last luminairein the circuit must not exceed the permissible cable length.Special requirements for distributors with functionalintegrity Typee DualGuard-S ESF... :The enclosures must be adapted to the masonry in such away that the enclosures are horizontal. The masonry mustbe designed to withstand fire for at least 30 minutes. Thefire resistance period of the masonry must not be affectedby the installation.The systems illustrated in these installation and operatinginstructions may differ in their modular configuration whendelivered. Special features of customer-specific designs aredescribed in the project documents to be ordered separately.WARNING!Work on the general supply network and the laying of load,signal and control lines as well as the connection of thebattery power supply may only be carried out by qualifiedelectricians with special knowledge of the legal and technicalprinciples for the installation and operation of emergencylighting systems. This also applies to the initial commissioningor re-commissioning of the emergency lighting system or theDualGuard-S system.Take all necessary measures for occupational safety!In addition to compliance with general technical standardsand procedures, this includes, in particular, compliance withall special notes and instructions.NOTE!All connecting cables may only be laid in accordance withthe relevant electrical engineering directives and standards(e.g. DIN VDE 100 series of standards).In addition, observe all national directives and regulations ofthe country in which the system is installed and operated.Secure all cable inlets and outlets of the DualGuard-S cabi-net against mechanical damage to the cables or moistureingress using the M cable glands or rubber seals providedfor this purpose.