131Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de54 DualGuard-S ESF30 US 30P54 DualGuard-S ESF30 US 30PThe DualGuard-S ESF30 US 30P sub-station with functionalintegrity of 30 minutes according to EN 50171 and MLARsupplies safety and escape sign luminaires 230V / 216VAC/DC and is particularly suitable in building areas whereit is not possible to accommodate the safety-related distri-bution boxes in a separate electrical operating room sepa-rate from the general power supply. The automatic testdevice and individual luminaire monitoring with individualstatus and name indication per luminaire in conjunctionwith system-related ECG / LED supply module includingmonitoring module without additional data line reports andadditionally proclaims the operating status of the externalphase monitor modules.Consisting of:Fire protection housing as floor standing cabinet with cableentry from above, HMI touch display built-in, ACU DGController, PSU power supply module.Preassembled mounting system for installation of:Up to 30 pcs circuit modulesTechnical description FieldDimensions (W x H x D): 2278x918x604 mmColour: RAL 7035Weight: 330 kgAssembly: GroundmontageDegree of protection: IP42Protection class: IAmbient temperature: -5°C to +35°CDegree of pollution: 2Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3Rated voltage (Mains): UN = 230 V AC B4Rated current (Mains): IN = 20 ARated voltage (Battery): 216 V DC B4Rated current (Battery): IN =20 ARated Frequency: 50 / 60 HzOvervoltage category: Mains: III / Battery: IIMax. connected load: At +35°C < 4,3 KWMaximum numbers of modules:Controller ACU DG / HMI 1 A1PSU 1 C1SKU.1 CG-S: C2-F1x6A 0-302x3A 0-304x1,5A 0-15Max. numbers luminaire circuits: 60 A2-3Terminals:ACU DG 2,5mm² Rigid/ 1,5mm² flexible A1Luminaire circuits 4 mm² Rigid/flexible A2-3Battery feed 16 mm² Rigid/flexible A4Battery through-wiring 16 mm² Rigid/flexible A4Mains feed 16 mm² Rigid/flexible A4Mains through-wiring 16 mm² Rigid/flexible A41 2 3 4ABCD