96 Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de41 DualGuard-S 12C41 DualGuard-S 12CThe DualGuard-S 12C in IP21 (IP31 optional) version withindividual cable entry in accordance with EN 50171 is sui-table for supplying up to 48 circuits for safety and escapesign luminaires 230V / 216V AC/DC in the power range upto 7.5KW. A shunting feeder for mains and battery enablesthe connection of a sub-station of type DualGuard US,DualGuard-S ESF30 and DualGuard-S SOU. The wiringsystem with rounded mounting fields does without classiccable ducts and, in combination with the natural ventilationand the large ventilation slots of the mounted modules,ensures a homogeneous control cabinet climate which hasbeen proven by heating tests in accordance with EN 61439-1 under nominal load conditions. The clear, self-explanatoryinternal modular field structure, taking contact protectioninto account, rounds off the appearance.The extensive catalogue of cabinet accessories such asspecial locks, door hinges right/left, cable entries, bases invarious heights, IP31 retrofit kits and IP54 on request offersthe right solution for most customer-specific requirementswithout long delivery times.The colour touch display with automatic testing device andindividual luminaire monitoring with individual status andname indication per luminaire in conjunction with system-related ECG / LED supply module including monitoringmodule without additional data line reports and records theoperating status of the external phase monitor modules,the insulation monitoring device as well as the batterystrings and, if battery block monitoring technology is used,the operating status of each individual battery block.1 2 3 4ABCD