I.L.15.01.T.K. Page 7Effective June 20005. Performance SpecificationsThe performance specifications for the ATS-MP1 Controller Board are given in Table 2:Table 2 – Performance SpecificationsInput Control Voltage (50-150)% of V(IN,RMS) 50/60 HzVoltage Measurements of: Normal Source VABNormal Source V BCNormal Source V CAEmergency Source V ABEmergency Source V BCEmergency Source V CAVoltage Measurement Range: 0 to 360 VAC RMS (50/60Hz) – MP10 to 750 VAC RMS (50/60Hz) – MP1-EVoltage Measurement Accuracy: ± 2% of reading over the monitoring rangeFrequency Measurements of: Normal Source (S1), Emergency Source (S2)Frequency Measurement Range: 40 Hz to 70 HzFrequency Measurement Accuracy ± 0.3 Hz over the measurement rangeUndervoltage Dropout Range: 50% to 97% of the nominal system voltageUndervoltage Pickup Range: (Dropout +2%) to 99% of the nominal system voltageOvervoltage Dropout Range: 105% to 120% of the nominal system voltageOvervoltage Pickup Range: 103% to (Dropout –2%) of the nominal system voltageUnderfrequency Dropout Range: 90% to 97% of the nominal system frequencyUnderfrequency Pickup Range: (Dropout + 1Hz) to 99% of the nominal system frequencyOverfrequency Dropout Range: 103% to 110% of the nominal system frequencyOverfrequency Pickup Range: 101% to (Dropout – 1Hz) of the nominal system frequencyOperating Temperature Range -20°C to + 70°CStorage Temperature Range -35°C to + 85°COperating Humidity 0 to 95% relative humidity (non-condensing)Generator Start Relay 5A, 1/6 HP @ 250VAC5A @ 30VDC with a 30W maximum loadAlarm Relay 10A, 1-3 HP @ 250VAC10A @ 30VDCTable 3 - Applicable Test StandardsUL 991Canadian Standards Association Conformance (CSA)UL 1008 / CSA 22.2 No 178.22Dielectric testFCC Part 15Conducted/Radiated Emissions (Class A)CISPR 11Conducted/Radiated Emissions (Class A)IEC 1000-2Electrostatic Discharge testIEC 1000-3Radiated Susceptibility testsIEC 1000-4Fast Transient testsIEC 1000-5Surge Withstand tests