I.L.15.01.T.K. Page 15Effective June 20009. Program Setpoints MenuThis table is a guide to the program setpoints menu. An explanation is given for each prompt thatwill appear as the Menu Select key is pressed.ProgramSetpoint DisplaySetpointPossibilitiesDisplayExplanationLang: English, French Language the controller displays messagesCurrent Day: Mon-Sun Current Day – requires to only be set onceCurrent Hour: 0-23 Current HourCurrent Min: 0-60 Current MinNom.Volt: 110 VAC – 240 VAC110VAC – 600VACSystem operating voltageNom .Freq: 50Hz or 60Hz. System operating frequencyPhases: 1 or 3 Single phase or Three Phase systemTDNE: 0 sec. to 1800 sec. Time Delay Normal to EmergencyTDES: 0 sec. to 120 sec. Time Delay Engine StartTDEN: 0 sec. to 1800 sec. Time Delay Emergency to NormalTDEC: 0 sec. to 1800 sec. Time Delay Engine CooldownTDN: -none-, N to E, E to N,globalTime Delay in Neutral position. Can beselected when transferring in one direction onlyor bothTDN: 0 to 120 sec. Time Delay NeutralTPRE: 0 to 255 sec Pre-Transfer Time DelayN-UV-DO: 50% to 99% of nominal Source 1 Undervoltage Dropout (% of nominal)N-UV-PU: (dropout +2%) to 99% Source 1 Undervoltage Pickup (% of nominal)E-UV-DO: 50% to 99% Source 2 Undervoltage Dropout (% of nominal)E-UV-PU: (dropout +2%) to 99% Source 2 Undervoltage Pickup (% of nominal)N-OV-DO: 105% to 120% Source 1 Overvoltage Dropout (% of nominal)N-OV-PU: (dropout -2%) to 120% Source 1 Overvoltage Pickup (% of nominal)E-OV-DO: 105% to 120% Source 2 Overvoltage Dropout (% of nominal)E-OV-PU: (dropout -2%) to 120% Source 2 Overvoltage Pickup (% of nominal)N-UF-DO: 90% to 99% of nominal Source 1 Underfrequency Dropout (Hz)N-UF-PU: (dropout +1Hz) – 99% Source 1 Underfrequency Pickup (Hz)E-UF-DO: 90% to 99% of nominal Source 2 Underfrequency Dropout (Hz)E-UF-PU: (dropout +1Hz) – 99% Source 2 Underfrequency Pickup (Hz)N-OF-DO: 103% to 110% Source 1 Overfrequency Dropout (Hz)N-OF-PU: (dropout –1Hz) – 110% Source 1 Overfrequency Pickup (Hz)E-OF-DO: 103% to 110% Source 2 Overfrequency Dropout (Hz)E-OF-PU: (dropout –1Hz) – 110% Source 2 Overfrequency Pickup (Hz)Pref.Src: enable or disable Preferred source enable or disableP.S. Select S1, S2 or none Preferred source select. Source 1(Normal),Source 2(Emergency) or None (sourcecurrently connected)Man. Retransf. Y or N Pushbutton input for manual return to normalTest/Area Prot Y or N Test/Area protection enable or disablePlant Exerciser: Y or N Plant Exerciser enabled or disabledPE Load Transf: Y or N Plant Exerciser Engine test with or without loadEngine Run: 0 – 600min. Engine run time on exerciseTest Day: --- ,or Mon-Sun Plant Exerciser Day of the weekTest Hour: 0-23 Plant Exerciser HourTest Min: 0-60 Plant Exerciser Test MinuteNote: Highlighted options are exclusive to the MP1-E Controller