Page 124 IM02601004E www.eaton.8 Setup on the Web Server Pages• The graphic size must be 143 pixels by 86 pixels. If it is larger than that, the meter will crop thegraphic to that size (cropping occurs on the right and bottom).• You must limit the color depth to 24 bit color or lower. The meter doesn’t support 32 bit colormodels.To add a custom graphic:1. Right-click the graphic.2. Choose Select Custom Graphic...3. In the Open dialog box, browse to the file on your local file system that you wish to upload.4. Select the file (its name should appear in the File Name field).5. Click the Select button.To revert to the default graphic:1. Right-click the graphic2. Choose Revert to PXM Photo (Default).QUICK SETUPThe Quick Setup page provides quick access to the most common configuration settings.NOTE: Only users with Wiring and Meter configuration permissions will be able to edit the QuickSetup.The Quick Setup page provides access to:• The Wiring Configuration selection• Enable/disable the Neutral Current (In), Ground Current (Ig), Calculated Neutral Current(In) and Calculated Ground Current (Ig)• Phase Rotation and Frequency selections• Line-to-Line Voltage, the Potential Transformer (PT) Ratio, the Current Transformer (CTRatio), the Ground CT, and the Neutral CT selections• Energy units display format, such as meter IDNOTE: If Neutral Current is selected, Calculated Neutral Current can NOT be selected and vice-versa. If Ground Current is selected, Calculated Ground Current can NOT be selected and vice-versa.Select one of the following wiring configurations based on the installation:• Single phase 2 wire (1CT)• Single phase 3 wire (2CT)• 3 Phase, 3 wire (Delta 3 CT)• 3 Phase, 4 wire (Y 3CT)• 3 Phase, 3 wire (Delta 2CT)• 3 Phase, 4 wire (Y 3 CT, 2V) 2 1/2 Element• 3 Phase, 4 wire (center tapped Delta 3 CT)Selecting Measure Ig allows you to view actual ground current. When Calculate Ig is selected, themeter estimates the ground current based on 3 phase and neutral current unbalance. SelectingMeasure In allow you to view actual neutral current based on the 3 phase current unbalance. WhenCalculate In is selected, the meter estimates the neutral current.