www.eaton.com IM02601004E Page 257F Specifications12-18 AWG, wire ferrules recommendedMeter PXMIO Discrete Inputs (IO1)Qty 8 common circuits IO1.1-1.824V internal source IO1.9To drive external dry contactInput impedance ~ 2.2K ohmInput current draw ~ 10 mAMinimum pulse width 10 millisecondMaximum pulse rate 20 HzCommon TVS clamped to ground ~ 300VWiring to 9 position removable terminal plug12-18 AWG, wire ferrules recommendedMeter PXMIO Solid-State Outputs (IO2)Qty 2 – Form A NO Bidirectional FETIsolation Circuit to ground 2KV /1 min.Isolation SS1 to SS2 2KV / 1 min.Maximum external source voltage 30VdcLine to Line TVS clamp at 32VdcMaximum load current 100 mA.Minimum pulse width 20millisecondsFixed 25milliseconds for Pulse Initiator functionMaximum pulse rate 25HzWiring to 4 position removable terminal plug12-18 AWG, wire ferrules recommendedMeter PXMIO Relay Outputs (IO3)Qty 3 - Form C Relays (both NO=A and NC=B contacts)Rated Current Voltage 5 A/30 Vdc, 100 - 240 VacIsolation circuit to ground 2,500 V / 1 minuteIsolation Relay to Relay circuit 2,500 V / 1 minuteContacts MOV protected at ~300VLifetime 5 A load 1,000,000 cyclesResponse Turn-On/Off Time ~ 20 - 30 msecWiring to 9 position removable terminal plug12-18 AWG, wire ferrules recommendedMetering inputsCurrent Inputs CT1-5 (Each channel)Rating 5 A secondary nominal,20 A continuous maxMetering Range 0.05 to 20ABurden < 10 mohmOverload Withstand500 A ac / 1 sec, non-repeatingAccuracy0.05% of reading + .01% of full scale (50 mA to 20A)Wiring to removable terminal plugScrew down coverRange 10 AWG - 18 AWGSafety Insulation Rating600 V all CT circuits to groundInstallation Category CAT IIIDielectric WithstandAll inputs to ground 3500 Vac / 1 minADC ConversionSpecifications, Con’t.