www.eaton.com IM02601004E Page 1338 Setup on the Web Server PagesFor example, if 15 minutes is selected, the demand calculation will be performed and the demandvalues will be updated every 15 minutes.With a sliding window setting, the Power Xpert Meter provides a rolling average; you select theinterval period and the subinterval period. For example, if you select 15 minutes as the demandinterval and 5 minutes as the subinterval, the demand will calculate every 5 minutes using the 3subinterval values (15 = 5X3). The interval and subinterval value may be 1 to 60 minutes. If bothvalues are the same, the demand interval is considered the fixed interval. A fixed interval periodshould be evenly divided by the subinterval value in case of a sliding interval.Locating Demand Setup on the WebFrom the Setup Main Page, Click Meter Setup & Commissioning from the tree structure on the leftside of the page. The tree structure will expand to list Security, Compensation, Metering, I/O, Clock,Communications and System. Click Metering. The tree structure will expand to list Demand, TOU,Load Profile and PQ Index. Click Demand. The page will update to list all the current Demand set-tings.Use the Edit button in the top right corner of the page to edit Demand settings. When Edit is se-lected, the page will update to display radio buttons for use in modifying settings. When a selectionis made, the appropriate interval periods can be entered. Click the OK button at the top of the pagewhen entries are completed.