www.eaton.com IM02601004E Page 1258 Setup on the Web Server PagesNOTE: When both Measure In and Calculate In are selected, Measure In overrides the setting.Enter the nominal line to line voltage. The Nominal line to line voltage value is used as a referencefor swells and sags monitoring.Select the Phase Rotation based on the Phase Rotation of the Input Voltages. Select the NominalFrequency of the Input Voltages from the Frequency list.Locating Quick Setup On The Web1. From the Setup Main Page, select Quick Setup from the tree structure. The page will update tolist all the current settings for Quick Setup. An Edit and an OK button will appear at the top ofthe page.2. Click Edit to change any of the listed settings.3. Click OK when new entries are completed.CONFIGURATION FILESConfiguration files can be downloaded to your local file system and then uploaded from your localfile system to a meter. This is a handy convenience feature, especially if you’re setting up multiplemeters with either the same or similar settings. You can set up one meter, download the configura-tion file to your local computer, and then upload that same configuration file to other meters. If youwant a hardcopy version of the meter settings, you can also create a formatted printout,Note: The configuration file is actually a ZIP file that contains multiple files, each with configurationsettings for a different aspect of the meter setup.To download the current configuration file:1. Click Save Config. File.2. Give the file a name (the dialog will fill in the .zip) extension.3. Click Save.To upload a configuration file to a meter:1. Click Load a Config. File.2. Select a .zip file.