www.eaton.com IM02601004E Page 1318 Setup on the Web Server PagesLocatingSubcycleDisturbance Setup on the WebFrom the Setup Main Page select Triggers from the tree structure on the left side of the page. Thetree structure will expand to list Out of Limits, Demand Overload, ITIC, Fast Transient and SubcycleDisturbance. Click Subcycle Disturbance. The page will update to list current settings.Use the Edit button at the bottom of the page to edit settings. When Edit is selected, the page willdisplay drop down boxes and check boxes for use in changing current settings. Click the Done but-ton at the bottom of the page when entries are completed.METER SETUP AND COMMISSIONING SETUPThe Meter Setup and Commissioning section of the Power Xpert Meter is broken into the followingcategories: Security, Compensation, Metering, I/O, Clock, Communication and System. These cat-egories contain setup information for Time of Use, PQ Index, Pulse Initiation, Hardware, Firmware,etc. Security was discussed earlier in this section. The remainder of the pages in this category willbe discussed below.COMPENSATION SETUPThe Compensation setup page allows you to compensate for errors within their PT and/or CT. Thevalue entered is used by the meter to multiply with respective to voltage and current channels. Thevalid range is -10 to 10. A CT Compensation value with a negative sign could be used to reversethe sign of measured current. This allows you to correct the polarity if the CT wires are incorrectly