5-44 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5IEC 61850 protocol configuration settings are accessed through software panels that are selected either in the OnlineWindow area (see figure) or the Offline Window area in the EnerVista software.The EnerVista software also includes an interface that is compatible with firmware versions 5.0 to 7.2 to configuresubscribers. Use the Simplified GOOSE Configurator in the Offline Window area.Figure 5-10: IEC 61850 protocol panel in EnerVista softwareThe IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and clickan option on the left to display its panel on the right. The following figure shows an example for Server Configuration. TheSETTING column contains the names of the settings, and the PARAMETER column is used to enter the settings. Hoveringthe mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its locationin SCL files.Figure 5-11: IEC 61850 panelOpening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the C70.This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both thosethat are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model