5-128 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALSYSTEM SETUP CHAPTER 5: SETTINGS5A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Information toprogram the settings is covered here. These features are provided for two or more breakers; a user can use only thoseportions of the design relevant to a single breaker, which must be breaker 1.The number of breaker control elements depends on the number of CT/VT modules specified with the C70. The followingsettings are available for each breaker control element.BREAKER 1 FUNCTION — This setting enables and disables the operation of the breaker control feature.BREAKER1 PUSH BUTTON CONTROL — Set to “Enable” to allow faceplate pushbutton operations.BREAKER 1 NAME — Assign a user-defined name (up to six characters) to the breaker. This name is used in flash messagesrelated to breaker 1.BREAKER 1 MODE — Selects “3-Pole” mode, where all breaker poles are operated simultaneously, or “1-Pole” mode where allbreaker poles are operated either independently or simultaneously.BREAKER 1 OPEN — Selects an operand that creates a programmable signal to operate an output relay to open breaker 1.BREAKER 1 BLK OPEN — Selects an operand that prevents opening of the breaker. This setting can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA. BREAKER 1 MODE:3-PoleRange: 3-Pole, 1-Pole BREAKER 1 OPEN:OffRange: FlexLogic operand BREAKER 1 BLK OPEN:OffRange: FlexLogic operand BREAKER 1 CLOSE:OffRange: FlexLogic operand BREAKER 1 BLK CLOSE:OffRange: FlexLogic operand BREAKER1 ΦA/3P CLSD:OffRange: FlexLogic operand BREAKER1 ΦA/3P OPND:OffRange: FlexLogic operand BREAKER 1 ΦB CLOSED:OffRange: FlexLogic operand BREAKER 1 ΦB OPENED:OffRange: FlexLogic operand BREAKER 1 ΦC CLOSED:OffRange: FlexLogic operand BREAKER 1 ΦC OPENED:OffRange: FlexLogic operand BREAKER 1 TOPERATE:70 msRange: 0 to 65535 s in steps of 1 BREAKER 1 EXT ALARM:OffRange: FlexLogic operand BREAKER 1 ALARMDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1TIME: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 BREAKER 1 OUT OF SV:OffRange: FlexLogic operand BREAKER 1 EVENTS:DisabledRange: Disabled, Enabled