7-10 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALTARGETS MENU CHAPTER 7: COMMANDS AND TARGETS7• The critical fail relay on the power supply module de-energizes• All other output relays de-energize and are prevented from further operation• The faceplate In Service LED indicator turns off• A RELAY OUT OF SERVICE event is recordedTo view error messages in EnerVista software:1. Access Actual Values > Records > Event Records.7.2.2.2 Major self-test error messagesThe major self-test errors are outlined in this section.• Latched target message: Yes.• Description of problem: One or more installed hardware modules is not compatible with the C70 order code.• How often the test is performed: Module dependent.• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failedmodule (for example, F8L).• Latched target message: No.• Description of problem: The configuration of modules does not match the order code stored in the C70.• How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every fiveseconds.• What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. Ifthe problem persists, contact the factory.• Latched target message: No.• Description of problem: A FlexLogic equation is incorrect.• How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified.• What to do: Finish all equation editing and use self tests to debug any errors.• Latched target message: No.• Description of problem: The PRODUCT SETUP INSTALLATION RELAY SETTINGS setting indicates the C70 is notprogrammed.• How often the test is performed: On power up and whenever the PRODUCT SETUP INSTALLATION RELAY SETTINGSsetting is altered.• What to do: Program all settings and then set PRODUCT SETUP INSTALLATION RELAY SETTINGS to “Programmed.”• Latched target message: Yes.• Description of problem: Module hardware failure detected. Module Failures 1 to 11 are major. The system can rebootfor four of these, as follows.INCOMPATIBLE H/W:Contact Factory (xxx)EQUIPMENT MISMATCH:with 2nd line detailFLEXLOGIC ERROR:with 2nd line detailUNIT NOT PROGRAMMED:Check SettingsMODULE FAILURE___:Contact Factory (xxx)