5-74 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5Figure 5-29: IEC 61850 Real Time ClockTmClkLTMS1.TmnsDelta.dbRange: 0.000 to 100.000 %Default: 0.000 %This setting is a deadband setting in which no action occurs.Deadband settingsA deadband is a range in which no action occurs, usually expressed as a percentage.The IEC 61850 panels contain hundreds of deadband settings, such as in the following panels: Product Setup > Real TimeClock, FlexLogic, Control Elements, and GGIO4. Each panel is not outlined here.Deadband setting names all end either with "DB" or .db. As they all work the same way, but each on a different analogvalue, a single description applicable to all deadband settings is given here. The analog value that each deadband settingapplies is usually obvious from the name of the setting. However, a tabulation of the analog values and their associateddeadband setting can be found in the UR Family Communications Guide.Figure 5-30: Deadband settings with .db suffix