CHAPTER 5: SETTINGS CONTROL ELEMENTSC70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 5-2315TRIP BUS 1 RESET — The trip bus output is reset when the operand assigned to this setting is asserted. Note that the RESET OPoperand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or viacommunications resets the trip bus output.Figure 5-123: Trip bus logic5.8.3 Setting groupsSETTINGS CONTROL ELEMENTS SETTING GROUPSThe setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPEDELEMENTS settings menu. The active setting group can be indicated on the front display of the UR by configuring User-Programmable LEDs to display the state of the SETTING GROUP ACT FlexLogic operands.SETTING GROUPS FUNCTION — When Enabled, allows setting groups other than group 1 (the default active group) to beactivated. The default setting group is forced active while the SETTING GROUPS FUNCTION setting is Disabled. SETTING GROUPS SETTING GROUPSFUNCTION: EnabledRange: Disabled, Enabled SETTING GROUPS BLK:OffRange: FlexLogic operand GROUP 2 ACTIVATE ON:OffRange: FlexLogic operand GROUP 6 ACTIVATE ON:OffRange: FlexLogic operand GROUP 1 NAME: Range: up to 16 alphanumeric characters GROUP 6 NAME: Range: up to 16 alphanumeric characters SETTING GROUPEVENTS: DisabledRange: Disabled, Enabled