4-72 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUALFLEXLOGIC DESIGN USING ENGINEER CHAPTER 4: INTERFACES4WarningsWhen using the 'Reset OP' operand, a warning can appear indicating that this is a disabled feature. This means that theReset Settting's FlexLogic operand is set to OFF. Resetting of the relay can be done by pressing the reset button on the frontpanel of the relay or by sending a Reset command through communications.Table 4-4: Warning messages from compiling4.4.1.5 Rapidly add logic blocks in sequenceBlocks are added by clicking an element then clicking in the drawing area, or by dragging and dropping the element ontothe canvas. Blocks can be added rapidly in sequence, for example when you have inputs 1 to 10, without having to selectthe element each time.To rapidly add logic blocks:1. In Engineer, click File > Preferences. The window opens.2. Click the Editor entry.3. Enable the Repeat Symbol check box.4. Click the Ok button to save and exit from the window.5. In the logic diagram, select an element, then click in the drawing area to add it, click again to add a second box, andso on.Error Timer Timer used more than once(TIMER_ID, SheetReference)The same timer is used in more than one place in the editor. This meanseither the circuit that the Timer belongs to has been branched, or theTimer has been duplicated.Error Input Unrecognized Parameter(SYMBOL_ID,Name,SheetReference)An Input symbol is configured to an item that is not recognized by thecurrent order code and version. Possible cause: The order code and/orversion of the settings file was converted causing the input parameter tobecome unavailable.Category Block orgateaffectedMessage DescriptionMinor warning Input Input set to unused VO(SYMBOL_ID,Name,Sheet)An Input symbol is using an unassigned Virtual OutputMajor warning Tag-Out Tag-out not connected(TAG_ID,Sheet)A Tag-Out symbol has no inputMajor warning All Symbol not connected(SYMBOL_ID,Name,Sheet)A symbol’s input and/or output is not connected and is not part of aVO block. Draw the input and/or output to the block.Minor warning =VO Virtual Output n using defaultname (VO_ID,Sheet)The Assigned Virtual Output is using the default name. Change thename.Minor warning Input Input using default name(SYMBOL_ID,Name,Sheet)An Input symbol is using a Contact Input, Contact Output, DigitalElement, FlexElement, or Digital Counter set to the default name.Change the name so that it is unique.Setting warning Input Input using disabled feature(SYMBOL_ID,Name,Sheet)An Input symbol is using a disabled Virtual Input, Contact Input, DigitalElement, FlexElement, Digital Counter, Control Pushbutton,Programmable Pushbutton, Contact Output, or Protection/MonitoringElement. Enable it and try again.Major warning Input Input set to OFF(SYMBOL_ID,Sheet)An Input symbol is set to OFFMajor warning Input Input set to ON(SYMBOL_ID,Sheet)An Input symbol is set to ONSetting warning Input Contact Output Operate is OFF(SYMBOL_ID, Contacts)The symbol block is using the default setting of OFFSetting warning Input Contact Output Seal-In is OFF(SYMBOL_ID, Contacts)The symbol block is using the default setting of OFFCategory Block or gateaffectedMessage Description