CHAPTER 5: SETTINGS PRODUCT SETUPF60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-1055The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation receivedfrom the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.If the F60 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in thecontrol field of the response).For any change to take effect, restart the relay.SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-103 IEC103 INPUTS MEASURANDS IEC103 INPUTS MEASURANDS ASDU 1See below ASDU 4 ASDU 1 ASDU 1 TYP:9Range: 3 or 9 ASDU 1 FUN:0Range: 0 to 255 in steps of 1 ASDU 1 INF:0Range: 0 to 255 in steps of 1 ASDU 1 SCAN TOUT:0Range: 0 to 1000 s in steps of 1 ASDU 1 ANALOG 1OffRange: FlexAnalog parameter ASDU 1 ANALOG 1FACTOR: 1.000Range: 0.000 to 65.535 in steps of 0.001 ASDU 1 ANALOG 1OFFSET: 0Range: -32768 to 32767 in steps of 1 ASDU 1 ANALOG 9OffRange: FlexAnalog parameter ASDU 1 ANALOG 9FACTOR: 1.000Range: 0.000 to 65.535 in steps of 0.001 ASDU 1 ANALOG 9OFFSET: 0Range: -32768 to 32767 in steps of 1 ASDU 4 ASDU 4 TYP:9Range: 3 or 9 ASDU 4 FUN:0Range: 0 to 255 in steps of 1 ASDU 4 INF:0Range: 0 to 255 in steps of 1 ASDU 4 SCAN TOUT:0Range: 0 to 1000 s in steps of 1 ASDU 4 ANALOG 1OffRange: FlexAnalog parameter ASDU 4 ANALOG 1FACTOR: 1.000Range: 0.000 to 65.535 in steps of 0.001