4-18 L60 Line Phase Comparison System GE Multilin4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES4Figure 4–20: LED PANELS 2 AND 3 (INDEX TEMPLATE)DEFAULT LABELS FOR LED PANEL 2:The default labels are intended to represent:• GROUP 1...6: The illuminated GROUP is the active settings group.• BREAKER 1(2) OPEN: The breaker is open.• BREAKER 1(2) CLOSED: The breaker is closed.• BREAKER 1(2) TROUBLE: A problem related to the breaker has been detected.• SYNCHROCHECK NO1(2) IN-SYNCH: Voltages have satisfied the synchrocheck element.• RECLOSE ENABLED: The recloser is operational.• RECLOSE DISABLED: The recloser is not operational.• RECLOSE IN PROGRESS: A reclose operation is in progress.• RECLOSE LOCKED OUT: The recloser is not operational and requires a reset.Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six settinggroups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting groups.Please note that the LEDs, despite their default labels, are fully user-programmable.The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match thepre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. TheLEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explainedin the following section.Figure 4–21: LED PANEL 2 (DEFAULT LABELS)4.3.3 CUSTOM LABELING OF LEDSa) ENHANCED FACEPLATEThe following procedure requires the pre-requisites listed below.• EnerVista UR Setup software is installed and operational.• The L60 settings have been saved to a settings file.USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LEDS842782A1.CDRNOTE842784A1.CDR