5-238 L60 Line Phase Comparison System GE Multilin5.6 CONTROL ELEMENTS 5 SETTINGS5c) BREAKER FLASHOVERPATH: SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS BREAKER FLASHOVER 1(2)The detection of the breaker flashover is based on the following condition:1. Breaker open,2. Voltage difference drop, and3. Measured flashover current through the breaker.Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available acrossthe breaker. BREAKER FLASHOVER 1BKR 1 FLSHOVRFUNCTION: DisabledRange: Disabled, EnabledMESSAGE BKR 1 FLSHOVR SIDE 1SRC: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE BKR 1 FLSHOVR SIDE 2SRC: NoneRange: None, SRC 1, SRC 2, SRC 3, SRC 4MESSAGE BKR 1 STATUS CLSD A:OffRange: FlexLogic™ operandMESSAGE BKR 1 STATUS CLSD B:OffRange: FlexLogic™ operandMESSAGE BKR 1 STATUS CLSD C:OffRange: FlexLogic™ operandMESSAGE BKR 1 FLSHOVR V PKP:0.850 puRange: 0.000 to 1.500 pu in steps of 0.001MESSAGE BKR 1 FLSHOVR DIFF VPKP: 1000 VRange: 0 to 100000 V in steps of 1MESSAGE BKR 1 FLSHOVR AMPPKP: 0.600 puRange: 0.000 to 1.500 pu in steps of 0.001MESSAGE BKR 1 FLSHOVR PKPDELAY: 0.100 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BKR 1 FLSHOVR SPV A:OffRange: FlexLogic™ operandMESSAGE BKR 1 FLSHOVR SPV B:OffRange: FlexLogic™ operandMESSAGE BKR 1 FLSHOVR SPV C:OffRange: FlexLogic™ operandMESSAGE BKR 1 FLSHOVR BLOCK:OffRange: FlexLogic™ operandMESSAGE BKR 1 FLSHOVRTARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE BKR 1 FLSHOVREVENTS: DisabledRange: Disabled, Enabled