B-22 L60 Line Phase Comparison System GE MultilinB.4 MEMORY MAPPING APPENDIX BBData Logger (Read/Write Setting)4181 Data Logger Channel Settings (16 items) --- --- --- F600 04191 Data Logger Mode 0 to 1 --- 1 F260 0 (Continuous)4192 Data Logger Trigger 0 to 65535 --- 1 F300 04193 Data Logger Rate 15 to 3600000 ms 1 F003 60000Clock (Read/Write Command)41A0 Real Time Clock Set Time 0 to 235959 --- 1 F050 0Clock (Read/Write Setting)41A2 SR Date Format 0 to 4294967295 --- 1 F051 041A4 SR Time Format 0 to 4294967295 --- 1 F052 041A6 IRIG-B Signal Type 0 to 2 --- 1 F114 0 (None)41A7 Clock Events Enable / Disable 0 to 1 --- 1 F102 0 (Disabled)41A8 Time Zone Offset from UTC –24 to 24 hours 0.5 F002 041A9 Daylight Savings Time (DST) Function 0 to 1 --- 1 F102 0 (Disabled)41AA Daylight Savings Time (DST) Start Month 0 to 11 --- 1 F237 0 (January)41AB Daylight Savings Time (DST) Start Day 0 to 6 --- 1 F238 0 (Sunday)41AC Daylight Savings Time (DST) Start Day Instance 0 to 4 --- 1 F239 0 (First)41AD Daylight Savings Time (DST) Start Hour 0 to 23 --- 1 F001 241AE Daylight Savings Time (DST) Stop Month 0 to 11 --- 1 F237 0 (January)41AF Daylight Savings Time (DST) Stop Day 0 to 6 --- 1 F238 0 (Sunday)41B0 Daylight Savings Time (DST) Stop Day Instance 0 to 4 --- 1 F239 0 (First)41B1 Daylight Savings Time (DST) Stop Hour 0 to 23 --- 1 F001 2Fault Report Commands (Read/Write Command)41B2 Fault Reports Clear Data Command 0 to 1 --- 1 F126 0 (No)Oscillography (Read/Write Setting)41C0 Oscillography Number of Records 1 to 64 --- 1 F001 1541C1 Oscillography Trigger Mode 0 to 1 --- 1 F118 0 (Auto. Overwrite)41C2 Oscillography Trigger Position 0 to 100 % 1 F001 5041C3 Oscillography Trigger Source 0 to 65535 --- 1 F300 041C4 Oscillography AC Input Waveforms 0 to 4 --- 1 F183 2 (16 samples/cycle)41D0 Oscillography Analog Channel n (16 items) 0 to 65535 --- 1 F600 04200 Oscillography Digital Channel n (63 items) 0 to 65535 --- 1 F300 0Trip and Alarm LEDs (Read/Write Setting)4260 Trip LED Input FlexLogic Operand 0 to 65535 --- 1 F300 04261 Alarm LED Input FlexLogic Operand 0 to 65535 --- 1 F300 0User Programmable LEDs (Read/Write Setting) (48 modules)4280 FlexLogic™ Operand to Activate LED 0 to 65535 --- 1 F300 04281 User LED type (latched or self-resetting) 0 to 1 --- 1 F127 1 (Self-Reset)4282 ...Repeated for User-Programmable LED 24284 ...Repeated for User-Programmable LED 34286 ...Repeated for User-Programmable LED 44288 ...Repeated for User-Programmable LED 5428A ...Repeated for User-Programmable LED 6428C ...Repeated for User-Programmable LED 7428E ...Repeated for User-Programmable LED 84290 ...Repeated for User-Programmable LED 94292 ...Repeated for User-Programmable LED 104294 ...Repeated for User-Programmable LED 114296 ...Repeated for User-Programmable LED 124298 ...Repeated for User-Programmable LED 13429A ...Repeated for User-Programmable LED 14429C ...Repeated for User-Programmable LED 15429E ...Repeated for User-Programmable LED 1642A0 ...Repeated for User-Programmable LED 17Table B–10: MODBUS MEMORY MAP (Sheet 14 of 57)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT