5-40 L60 Line Phase Comparison System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS55.2.7 FAULT REPORTSPATH: SETTINGS PRODUCT SETUP FAULT REPORTS FAULT REPORT 1The L60 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well asthe characteristics of the line or feeder, are entered in this menu.The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained inthe FaultReport.txt file includes:• Fault report number.• Name of the relay, programmed by the user.• Firmware revision of the relay.• Date and time of trigger.• Name of trigger (specific operand).• Line or feeder ID via the name of a configured signal source.• Active setting group at the time of trigger.• Pre-fault current and voltage phasors (two cycles before either a 50DD disturbance associated with fault report sourceor the trigger operate). Once a disturbance is detected, pre-fault phasors hold for 3 seconds waiting for the fault reporttrigger. If trigger does not occur within this time, the values are cleared to prepare for the next disturbance.• Fault current and voltage phasors (one cycle after the trigger).• Elements operated at the time of triggering.• Events: 9 before trigger and 7 after trigger (only available via the relay webpage).• Fault duration times for each breaker (created by the breaker arcing current feature). FAULT REPORT 1FAULT REPORT 1SOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE FAULT REPORT 1 TRIG:OffRange: FlexLogic™ operandMESSAGE FAULT REPORT 1 Z1MAG: 3.00 ΩRange: 0.01 to 250.00 ohms in steps of 0.01MESSAGE FAULT REPORT 1 Z1ANGLE: 75°Range: 25 to 90° in steps of 1MESSAGE FAULT REPORT 1 Z0MAG: 9.00 ΩRange: 0.01 to 650.00 ohms in steps of 0.01MESSAGE FAULT REPORT 1 Z0ANGLE: 75°Range: 25 to 90° in steps of 1MESSAGE FAULT REPORT 1 LINELENGTH UNITS: kmRange: km, milesMESSAGE FAULT REP 1 LENGTH(km ): 100.0Range: 0.0 to 2000.0 in steps of 0.1MESSAGE FAULT REPORT 1 VTSUBSTITUTION: NoneRange: None, I0, V0MESSAGE FAULT REP 1 SYSTEMZ0 MAG: 2.00 ΩRange: 0.01 to 650.00 ohms in steps of 0.01MESSAGE FAULT REP 1 SYSTEMZ0 ANGLE: 75°Range: 25 to 90° in steps of 1