B-42 L60 Line Phase Comparison System GE MultilinB.4 MEMORY MAPPING APPENDIX BB8D70 ...Repeated for Digital Element 458D84 ...Repeated for Digital Element 468D98 ...Repeated for Digital Element 478DAC ...Repeated for Digital Element 48Trip Bus (Read/Write Setting) (6 modules)8E00 Trip Bus 1 Function 0 to 1 --- 1 F102 0 (Disabled)8E01 Trip Bus 1 Block 0 to 65535 --- 1 F300 08E02 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 08E03 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 08E04 Trip Bus 1 Input 1 0 to 65535 --- 1 F300 08E05 Trip Bus 1 Input 2 0 to 65535 --- 1 F300 08E06 Trip Bus 1 Input 3 0 to 65535 --- 1 F300 08E07 Trip Bus 1 Input 4 0 to 65535 --- 1 F300 08E08 Trip Bus 1 Input 5 0 to 65535 --- 1 F300 08E09 Trip Bus 1 Input 6 0 to 65535 --- 1 F300 08E0A Trip Bus 1 Input 7 0 to 65535 --- 1 F300 08E0B Trip Bus 1 Input 8 0 to 65535 --- 1 F300 08E0C Trip Bus 1 Input 9 0 to 65535 --- 1 F300 08E0D Trip Bus 1 Input 10 0 to 65535 --- 1 F300 08E0E Trip Bus 1 Input 11 0 to 65535 --- 1 F300 08E0F Trip Bus 1 Input 12 0 to 65535 --- 1 F300 08E10 Trip Bus 1 Input 13 0 to 65535 --- 1 F300 08E11 Trip Bus 1 Input 14 0 to 65535 --- 1 F300 08E12 Trip Bus 1 Input 15 0 to 65535 --- 1 F300 08E13 Trip Bus 1 Input 16 0 to 65535 --- 1 F300 08E14 Trip Bus 1 Latching 0 to 1 --- 1 F102 0 (Disabled)8E15 Trip Bus 1 Reset 0 to 65535 --- 1 F300 08E16 Trip Bus 1 Target 0 to 2 --- 1 F109 0 (Self-reset)8E16 Trip Bus 1 Events 0 to 1 --- 1 F102 0 (Disabled)8E18 Reserved (8 items) 0 to 1 --- 1 F001 08E20 ...Repeated for Trip Bus 28E40 ...Repeated for Trip Bus 38E60 ...Repeated for Trip Bus 48E80 ...Repeated for Trip Bus 58EA0 ...Repeated for Trip Bus 6FlexElement (Read/Write Setting) (8 modules)9000 FlexElement™ 1 Function 0 to 1 --- 1 F102 0 (Disabled)9001 FlexElement™ 1 Name --- --- --- F206 “FxE 1”9004 FlexElement™ 1 InputP 0 to 65535 --- 1 F600 09005 FlexElement™ 1 InputM 0 to 65535 --- 1 F600 09006 FlexElement™ 1 Compare 0 to 1 --- 1 F516 0 (LEVEL)9007 FlexElement™ 1 Input 0 to 1 --- 1 F515 0 (SIGNED)9008 FlexElement™ 1 Direction 0 to 1 --- 1 F517 0 (OVER)9009 FlexElement™ 1 Hysteresis 0.1 to 50 % 0.1 F001 30900A FlexElement™ 1 Pickup -90 to 90 pu 0.001 F004 1000900C FlexElement™ 1 DeltaT Units 0 to 2 --- 1 F518 0 (Milliseconds)900D FlexElement™ 1 DeltaT 20 to 86400 --- 1 F003 20900F FlexElement™ 1 Pickup Delay 0 to 65.535 s 0.001 F001 09010 FlexElement™ 1 Reset Delay 0 to 65.535 s 0.001 F001 09011 FlexElement™ 1 Block 0 to 65535 --- 1 F300 09012 FlexElement™ 1 Target 0 to 2 --- 1 F109 0 (Self-reset)9013 FlexElement™ 1 Events 0 to 1 --- 1 F102 0 (Disabled)9014 ...Repeated for FlexElement™ 29028 ...Repeated for FlexElement™ 3Table B–10: MODBUS MEMORY MAP (Sheet 34 of 57)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT