6-6 L60 Line Phase Comparison System GE Multilin6.2 STATUS 6 ACTUAL VALUES6b) STATISTICSPATH: ACTUAL VALUES STATUS REMOTE DEVICES STATISTICS REMOTE DEVICE 1(16)Statistical data (two types) for up to 16 programmed remote devices is shown here.The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of atleast one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incrementedwhenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.6.2.10 DIGITAL COUNTERSPATH: ACTUAL VALUES STATUS DIGITAL COUNTERS DIGITAL COUNTERS Counter 1(8)The present status of the eight digital counters is shown here. The status of each counter, with the user-defined countername, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date andtime stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.6.2.11 SELECTOR SWITCHESPATH: ACTUAL VALUES STATUS SELECTOR SWITCHESThe display shows both the current position and the full range. The current position only (an integer from 0 through 7) is theactual value.6.2.12 FLEX STATESPATH: ACTUAL VALUES STATUS FLEX STATES REMOTE DEVICE 1REMOTE DEVICE 1StNum: 0MESSAGE REMOTE DEVICE 1SqNum: 0 DIGITAL COUNTERS Counter 1Counter 1 ACCUM:0MESSAGE Counter 1 FROZEN:0MESSAGE Counter 1 FROZEN:YYYY/MM/DD HH:MM:SSMESSAGE Counter 1 MICROS:0 SELECTOR SWITCHESSELECTOR SWITCH 1POSITION: 0/7Range: Current Position / 7MESSAGE SELECTOR SWITCH 2POSITION: 0/7Range: Current Position / 7 FLEX STATESPARAM 1: OffOffRange: Off, OnMESSAGE PARAM 2: OffOffRange: Off, On↓MESSAGE PARAM 256: OffOffRange: Off, On