7ANTRIEBSTECHNIK6 8 7KEB COMBIVERT F4-CName: Basis29.01.986Functional DescriptionParameter Sets© KEB Antriebstechnik, 1997All Rights reservedChapter Section PageDateParam. Adr. min max defaultENTERPROG.R/WStep12345 66.8.6 Used ParametersFr.0 2700h 4 4 4 -2 7 1 0 not via busFr.1 2701h 4 - - -2 7 1 0 not via keyboardFr.2 2702h 4 - 4 0 3 1 0 -Fr.3 2703h 4 - 4 0 255 1 0 -Fr.4 2704h 4 - 4 0 7 1 0 -Fr.5 2705h 4 4 - 0 2,55 s 0,01 s 0 -Fr.6 2706h 4 4 - 0 2,55 s 0,01 s 0 -Fr.9 2709h 4 - - -1 7 1 0 not via keyboard6.8.5 Parameter Set ONand OFF Delay(Fr.5, Fr.6)With these parameters the time is adjusted- by which the activation of a new set shall be delayed (Fr.5)- by which the deactivation of a set shall be delayed (Fr.6)At set changeover the turn-off time of the old set and the turn-on time of the new setare added up.Set 1Set 3Set 2Set 1Set 3Set 2Set 0Set 0Preselected setActual setPicture 6.8.5 ON and OFF delayExampleSet Fr.5 Fr.60 0 s 0 s1 2 s 0 s2 0 s 1 s3 2 s 2 s1: ON delay set 3 of 2s2: OFF delay set 3 of 2s3: OFF delay of set 2 of 1s +ON delay of set 1 of 2 s4: immediate changeover as no delay-time is adjusted5: OFF delay set 2 of 1s +ON delay of set 3 of 2s6: OFF delay of set 3 of 2s