7 - 8 en-938821/27.6 Parameter Table Not Conforming to Software VersionMessage displayed at initializationPARAMETER TABLE INDEX ERRORRE-INIT TABLE ?(Y):CommentThis is not a system fault but a warning before reset of the machine parameter table during CNC software updating.Switching to a new software version is achieved by replacing:- the memory board,or- part of the memory board (daughterboard).The existing parameter table may no longer conform to the new software version (the differences concern only a limitednumber of parameters).During the first reset following software updating, the system detects a different version of the parameter table andrequests re-initialisation of this table.ActionsAcknowledge the message. + YThe following message is displayed:EEPROM SAVING DONE ?(Y):There are two possibilities:The parameter table has been savedAcknowledge the message. + YThe system is available, but all the machine parameters have taken on their default values.Reload the parameter table (See table below).Parameter saving ActionsPaper printout Manually enter the new parameters(See Parameter manual)Magnetic storage Reload the parameters (See Parametermanual)Manually enter values for the parameters of the new version(See Parameter manual).Reset the system to take the parameters into account.