Overview Combination Fire/Burglary ApplicationsAFP-200 PN 15511:H2 10/14/2002 157Appendix E Combination Fire/Burglary ApplicationsE.1 OverviewThe control panel can be used as a combination Fire/Burglary and Burglary systemwhen installed, programmed, and operated according to the following:Table 58 Security Application RequirementsNotes for Table 58:1. The control panel uses the same trouble input connector for the door tamper switch(STS-200), the APS-6R, and the AVPS-24. If an APS-6R or AVPS-24 is installedand programmed, therefore, do not use the control panel in Fire/Burglaryapplications.2. A Combination fire/burglary listing does not include supervisory service.3. A security type circuit is designed to indicate an alarm on an open or short circuit,or a resistance change of 50% (plus or minus) from the end-of-line resistor value.A tamper switch installed in the cabinet will also indicate a security alarmwhenever the door is opened.E.2 InstallationE.2.1 Installation OverviewInstalling a combination Fire/Burglary application includes the following tasks:• Installing a Tamper Switch.• Wiring for Proprietary Security Alarm Applications.• Connecting to an AM2020/AFP1010 Receiving Unit.E.2.2 Installing a Tamper SwitchWire the control panel with the STS-200 security tamper switch kit. To do so, followthese instructions:1. Mount the STS-200 to the cabinet (Figure 148).2. Run the wiring behind the CPU board (Figure 148).3. Cut Jumper JP3.Task Refer toInstall an STS-200 Door Tamper Switch Figure 148 on page 158Wire the control panel for a securityapplicationFigure 149 on page 159Program a Monitor Module for asecurity applicationFigure 150 on page 160Configure the control panel keypad fora security applicationFigure 150 on page 160Technical Manuals Online! - http://www.tech-man.com