Installation Wiring a Signaling Line Circuit (SLC)56 AFP-200 PN 15511:H2 10/14/20022.9.11 Wiring a Notification Appliance Circuit (NAC) orControl CircuitControl and Relay Module OverviewThe FCM-1 is an addressable module that controls a Notification Appliance Circuit(NAC). Use the FCM-1 to route 24 VDC NAC Power for NFPA Style Y (Class B) andNFPA Style Z (Class A) notification circuits. Figure 38 shows control moduleconnections.Figure 38 FCM-1 Control Module ConnectionsThe FRM-1 is an addressable module which includes a Form-C dry contact relay whichcan be used to activate a variety of output circuits. Figure 39 shows relay moduleconnections.Figure 39 FRM-1 Relay Module ConnectionsRatings for the dry contacts on a Form-C relay module are:Resistive: 3.0 A @ 30 VDC max Non-coded applicationFurther rating information is available in the module document and data sheet.9 08 17 26 35 4Style D NAC (+)Style D NAC (–)Style B NAC (–)Style B NAC (+)no connectionno connectionSLC (–)SLC (+)24 VDC Power (–)24 VDC Power (+)Note: Polarity shown in alarm condition8 9101112131415012345 6 78 9012345 6 7TENSONESLOOPLOOP ADDRESSADDRESS89765987650123443210TENSONES8 9012345 6 78 9101112131415012345 6 789765987650123443210LOOPLOOPSLCSLC-frmC.cdrFRM-1NOCNCNOCNCTo next deviceon SLCFrom FACP or previous device on SLC loopSLC (+) TB6-3SLC (–) TB6-5Refer to the installationinstruction sheet supplied withthe control module foradditional information.Technical Manuals Online! - http://www.tech-man.com