Programming Getting Started68 AFP-200 PN 15511:H2 10/14/20023.2.4 Programming ShortcutsDuring programming, thecontrol panel automaticallyreturns to normal operationafter two minutes of inactivity.“Programming Shortcuts” on page 68 lists shortcuts that you can use whenprogramming the control panel.Table 14 Programming Shortcuts3.2.5 Upload and DownloadAn upload/download of the control panel may be done at any time by connecting apersonal computer to the EIA-232 port and running the off-line programming routine.Refer to the Veri•Fire on-line help program for more information.3.2.6 Key Programming TermsHere is a list of terms that apply to control panel programming.All Systems Normal message The message (up to 40 characters) in first two lines ofthe LCD display during normal system operation.Autoprogram A control panel programming function that automatically detects newdevices connected to the SLC, assigns default programming information, and alsodetermines the total number of programmed devices.CBE (Control-by-Event) A software function that provides a means to program avariety of output responses based on various initiating events.Control module Addressable module that switches power to a Style Y or Style Z NAC.CPU memory (Central Processing Unit) The nonvolatile element of the CPU thatcontains programming information for the control panel.custom label A custom label is a user-defined message in an LCD display thatidentifies a device.detector sensitivity A detector setting for an ionization or photoelectric detector thatdetermines the level at which a detector will activate.installed device An intelligent, addressable detector, control, monitor or relay moduleproperly addressed and installed in a fire alarm system.missing device A missing device is a detector or module removed from the SLC (TB6)that exists in the current program.Monitor module An addressable monitor module that monitors conventionalalarm-initiating devices.To Do thisTo save a point’sprogram intomemory duringAutoprogram orpoint programmingPress the ENTER key. After pressing the ENTER key, the autoprogramroutine displays the next new detector or module.To exit from ProgramChange or StatusChange operationsPress the BACKSPACE key until the All Systems Normal screen appears,or press the SYSTEM RESET key.To display the last19-character labelWhen the blinking cursor is over the first letter of the label field, pressthe zero key twice to display the label entered for the previous point. Ifthe last character of the label is a number, pressing the zero key a thirdtime will increment this number. Once you recall the label, you can editeach character of the label.Technical Manuals Online! - http://www.tech-man.com