Error92 I11 T11 192-120101 N6 - March 2004All errors lead to error status.Reaction 2: downramp with ìdeenergize rampî then apply brake (see on page 76)and deenergize.Reaction 5: De-energize immediately (with no ramp), close brake.Caution! A Z-axis may drop down due to the brake delay timesMost pending errors can be acknowledged with Quit!The following errors must be acknowledged with Power on:0x7381, 0x7382, 0x7391, 0x7392, 0x73A0The errors as well as the error history can be viewed in the C3 ServoManagerunder optimization (at the top right of the optimization window).7.1 Error listError code (hex): 0x2311Error: Monitor (Effective Motor Current)Error reaction: Reaction 2: downramp / apply brake / deenergize.Measure:Note: Adjustable monitoring (with motor parameter: thermal time constant andreference current)The current value can be read with the "Motor utilization" status display.An error message is generated for a motor load of 105%.Error code (hex): 0x2312Error: Device rms current monitoringError reaction: Reaction 2: downramp / apply brake / deenergize.Measure:Note: Adjustable monitoring (dependant on device parameters)The current value can be read with object 683.2 or the "Device utilization"status display.Error code (hex): 0x2320Error: Overcurrent (Power output Stage)Error reaction: Reaction 5: deenergize immediately (without ramps), apply brake.Measure: Check motor cableNote: Origin is a hardware signalError code (hex): 0x3210Error: DC bus voltage too highError reaction: Reaction 5: deenergize immediately (without ramps), apply brake.Measure:Note: The voltage on the output bus has exceeded the maximum permissiblevalue7. Error0x23110x23120x23200x3210