vacon 10 api vacon • 3724-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com66.2 Control I/OFigure 6.1: Vacon 10 I/OTerminal Signal Factory preset Description1 +10Vre Ref. voltage out Maximum load 10 mA2 AI1 Analog signal in 1 Freq. reference P) 0 - 10 V Ri = 200 k(min)3 GND I/O signal ground6 24Vout 24V output for DI's %, max. load 50 mA7 GND I/O signal ground8 DI1 Digital input 1 Start forward P) 0 - +30 V Ri = 12 k min9 DI2 Digital input 2 Start reverse P)10 DI3 Digital input 3 Fault reset P)A A RS485 signal A FB Communication NegativeB B RS485 signal B FB Communication Positive4 AI2 Analog signal in 2 PI actual value P) 0(4) - 20 mA, Ri = 2005 GND I/O signal ground13 GND I/O signal ground14 DI4 Digital input 4 Preset speed B0 P) 0 - +30 V Ri = 12 k(min)15 DI5 Digital input 5 Preset speed B1 P)16 DI6 Digital input 6 External fault P)18 AO Analog Output Output frequency P) 0(4) - 20 mA, RL = 50020 DO Digital signal out Active = READY P) Open collector, max.load 48V/50mA22 RO 13 Relay out 1 Active = RUN P) Max. switching load:250Vac/2A or 250Vdc/0,4A23 RO 1424 RO 22 Relay out 2 Active = FAULT P) Max. switching load:250Vac/2A or 250Vdc/0,4A25 RO 2126 RO 24Table 6.2: Vacon 10 default I/O configuration and connectionsP) = Programmable function, see parameter lists and descriptions,chapters 8 and 9.20ONOFFmA