parameters vacon • 5924-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com88.12Table 8.12: PI control parametersCode Parameter Min Max Unit Default ID NoteP15.1 Setpoint selec-tion 0 3 0 3320 = Fixed setpoint %1 = AI12 = AI23 = Fiel-bus(ProcessDataIn1)P15.2 Fixed setpoint 0,0 100,0 % 50,0 167 Fixed setpointP15.4 Feedback valueselection 0 2 1 3340 = AI11 = AI22 = Field-bus (Process-DataIn2)iiii P15.5 Feedback valueminumum 0,0 50,0 % 0,0 336 Value at minimum signalP15.6 Feedback valuemaximum 10,0 300,0 % 100,0 337 Value at maximum signalP15.7 P gain 0,0 1000,0 % 10,00 118 Proportional gainP15.8 I time 0,00 320,00 s 10,00 119 Integrative timeP15.10 Error inversion 0 1 0 3400 = Direct (Feedback < Set-point ->Increase PID out-put)1 = Inverted (Feedback >Setpoint ->Decrease PIDoutput)PI control parameters (Control panel: Menu PAR -> P15)NOTE! These parameters are shown, when P17.2 = 0.8.13 Application Setting (Control panel: Menu PAR -> P17)Code Parameter Min Max Unit Default ID NoteApplication Type 0 3 0 5400 = Basic1 = Pump2 = Fan drive3 = High TorqueNOTE! Visible only whenStartup wizard is active.P17.2 Parameterconceal 0 1 1 1150 = All parameters visible1 = Only quick setupparameter group visibleTable 8.13: Application Setting parametersi P17.1