58 • vacon parametersTel. +358 (0)201 2121 • Fax +358 (0)201 21220588.10 Protections (Control panel: Menu PAR -> P13)NOTE! These parameters are shown, when P17.2 = 0.8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14)NOTE! These parameters are shown, when P17.2 = 0.Code Parameter Min Max Unit Default ID NoteP13.1 Analog Input lowfault 0 2 1 7000 = No action1 = Alarm2 = Fault: CoastUnder voltagefault 1 2 2 7271 = No response (no faultgenerated but drive stillstops modulation)2 = Fault:CoastEarth fault 0 2 2 703 As parameter 13.1Output PhaseFault 0 2 2 702 As parameter 13.1Stall protection 0 2 0 709 As parameter 13.1Under load pro-tection 0 2 0 713 As parameter 13.1Motor thermalprotection 0 2 2 704 As parameter 13.1Mtp:Ambienttemperature -20 100 °C 40 705 Environment tempera-tionMtp:Zero speedcooling 0,0 150,0 % 40,0 706 Cooling as % at 0 speedMtp:Thermal timeconstant 1 200 min 45 707 Motor thermal time con-stantTable 8.10: ProtectionsCode Parameter Min Max Unit Default ID NoteAutomatic Reset 0 1 0 731 0 = Disabled1 = EnableWait time 0,10 10,00 s 0,50 717 Waiting time after faultTrial time 0,00 60,00 s 30,00 718 Maximum time for trialsRestart Function 0 2 2 7190 = Ramping1 = Flying2 = From Start FunctionTable 8.11: Fault autoreset parametersP13.2P13.3P13.4iiiiiiP13.5P13.6P13.7P13.8P13.9P13.10P14.1P14.2iiP14.3P14.5