parameter descriptions vacon • 6724-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com99.2 Start / stop setup (Control panel: Menu PAR -> P2)2.1 REMOTE CONTROL PLACE 1 SELECTIONWith this parameter, the user can select the active control place. The selec-tions are:0 = I / O terminal (frequency reference can be selected with P3.3)1 = FieldbusThe priority order of selecting the control place is:1. Force to I/O when the digital input of P5.13 (Force to I/O) is active.2. Loc/Rem button or P2.5 (Local/Remote) =1.3. Determined by P2.1 (Remote Control Place Selection).Note: You can select control place by pressing Loc / Rem button or with par.2.5, P2.1 will have no effect in local mode.Local = Keypad is the control placeRemote = I / O terminal or FieldBus2.2 START FUNCTIONThe user can select two start functions for Vacon 10 with this parameter:0 = Ramp startThe frequency converter starts from 0 Hz and accelerates to the setfrequency reference within the set acceleration time (See detailed de-scription: ID103). (Load inertia, torque or starting friction may causeprolonged acceleration times).1 = Flying startWith this function the drive identifies the speed of the motor and startsto the corresponding frequency immediately.Use this mode if the motor is rotating when the start command is giv-en. With the flying start, it is possible to ride through short mains volt-age interruptions.2.3 STOP FUNCTIONTwo stop functions can be selected in this application:0 = CoastingThe motor coasts to a halt without control from the frequency convert-er after the Stop command.